Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00639
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/25/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/18/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THESE PEDESTALS 1 THRU 12 NOT APPROVED PER LISTINGS-SEE PREVIOUS NOTES-THESE PEDESTALS WERE INSTALLED BY MEHL ELECTRIC |
|
12/12/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 13 THRU 28 |
|
10/31/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK #46 THRU 58 |
|
10/28/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/22/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK PEDESTALS 32 THRU 37 |
|
09/21/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO ENERGIZE 38 THRU 45 |
|
08/30/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK PEDESTAL #29, 30 AND 31 |
|
03/21/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK SERVICES M1, M2 AND M3 |
|
03/07/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SERVICE 'M3' TIGHTEN LOCK NUTS, BOND NIPPLES ONE SIDE BETWEEN DISC. AND PANEL 2) 'M1' NEEDS 22K BREAKERS TO MATCH PER MANUFACTURERS 3) 'M2' OK |
|
01/28/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SPOKE TO CONTRACTOR VIA TELEPHONE, NO REVISED PLANS YET OR CORRECTIONS TO SERVICE EQUIPMENT. ADVISED CONTRACTOR THAT NO FURTHER INSPECTIONS PERFORMED UNTIL OUTSTANDING CODE VIOLATIONS CORRECTED-SEE NOTES |
|
01/25/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK PEDESTALS 29,30 & 31 2) FINISH DISCONNECTS AND RACK 3) VERIFY LOADS FOR SITE LIGHTING ATTACHED TO 31-NOT ON PLANS |
|
12/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES PREVIOUS INSPECTION 2) MEETING ON SITE TODAY WITH BOB SMITH, LARRY MEHL AND RANDY (ELECTRICIAN) TO DISCUSS INSTALLATION REQUIREMENTS |
|
12/06/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PER MEETING WITH NEW ELECTRICAL CONTRACTOR MEHL ELECTRIC NO LONGER CONTRACTOR-CHANGE CONTRACTOR OF RECORD TO SHOW NEW ON PERMIT 2) OBTAIN APPROVED PLANS WITH LATEST REVISIONS 3) SEE NOTES PREVIOUS INSPECTION 4/16/10 FOR CORRECTION OF EQUIPMENT INSTALLED UNDER PREVIOUS CONTRACTOR |
|
12/02/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COULD NOT LOCATE CONTRACTOR-NO MSG 2) CONTRACTOR OF RECORD TO BE ON PERMIT 3) NOTE: NEW MH PEDESTAL ARE IN USE PRIOR TO INSPECTION APPROVAL. SEE NOTES FOR PROPER USE OF LISTED EQUIPMENT |
|
04/16/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSPECTION FOR M3 SERVICE, CORRECTIONS AS FOLLOWS: 1) FUSES NOT PER PLAN IN MAIN SERVICE DISCONNECT 2) EQUIPMENT GROUNDS SHOULD BE #3 CU PER 250.122 NEC 3) GROUND RODS NOT 10' APART AS SPECIFIED ON PLAN REF. 2006 IBC 106.3.1 AND 106.4 4) SUPPLY CONDUCTORS NOT PER PLAN, ALSO CONDUIT SIZE 5) CIRCUIT BREAKERS NOT RATED 22K PER PLAN 6) KO SEALS NEED TO BE LISTED FOR OUTDOOR USE AND APPLICATION 7) SERVICE DISCONNECT NOT RATED PER PLAN (200K) ? 8) SECURE GROUND ELECTRODE CONDUCTOR TO ENCLOSURE MC SERVICE DISCONNECT AND REMOTE PANEL: 1) CONDUIT REDUCING WASHER AT BOTTOM OF MAIN DISCONNECT NOT LISTED TYPE 2) NOTES #1,2,3,4,7 & 8 FROM 'M3' INSPECTION APPLICABLE TO 'M2' SERVICE 3) EXPOSED CONDUITS TO GALV. IMC PER PLAN M1 SERVICE: 1) NOTES FROM 'M3' INSPECTION APPLY #1,4,5,7 & 8 PEDESTAL INSPECTION TYPE OF 13: 1) NOT INSTALLED PER LISTING-SERVICE EQUIPMENT ONLY 110.3 NEC 2) NO BUSHING ON CONDUITY ENTRY INTO PEDESTAL 300.5-H AND 352.46 3) NEUTRAL AND EQUIPMENT GROUND TIED TOGETHER IN PEDESTAL 250.6 4) ILLEGAL DBL TAPING ON SUPPLY SIDE OF PEDESTAL 5) VERIFY SPLICES LISTED FOR WET LOCATION 314.30 NEC 6) DEVICES (RECEPTS) 4-WIRE NOT GROUNDED 250 NEC 7) INSTALL PERMANENT ADDRESS OR UNIT LABELS ON PEDESTALL 110.22 |