Permit: T10EL00639

Parcel: 106090110


Addresses:

1635 W ROGER RD #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL00639

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/25/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/18/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THESE PEDESTALS 1 THRU 12 NOT APPROVED PER LISTINGS-SEE PREVIOUS NOTES-THESE PEDESTALS WERE INSTALLED BY MEHL ELECTRIC
12/12/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK 13 THRU 28
10/31/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK #46 THRU 58
10/28/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/22/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK PEDESTALS 32 THRU 37
09/21/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TO ENERGIZE 38 THRU 45
08/30/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK PEDESTAL #29, 30 AND 31
03/21/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK SERVICES M1, M2 AND M3
03/07/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SERVICE 'M3' TIGHTEN LOCK NUTS, BOND NIPPLES ONE SIDE BETWEEN DISC. AND PANEL
2) 'M1' NEEDS 22K BREAKERS TO MATCH PER MANUFACTURERS
3) 'M2' OK
01/28/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPOKE TO CONTRACTOR VIA TELEPHONE, NO REVISED PLANS YET OR CORRECTIONS TO SERVICE EQUIPMENT. ADVISED CONTRACTOR THAT NO FURTHER INSPECTIONS PERFORMED UNTIL OUTSTANDING CODE VIOLATIONS CORRECTED-SEE NOTES
01/25/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK PEDESTALS 29,30 & 31
2) FINISH DISCONNECTS AND RACK
3) VERIFY LOADS FOR SITE LIGHTING ATTACHED TO 31-NOT ON PLANS
12/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES PREVIOUS INSPECTION
2) MEETING ON SITE TODAY WITH BOB SMITH, LARRY MEHL AND RANDY (ELECTRICIAN) TO DISCUSS INSTALLATION REQUIREMENTS
12/06/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PER MEETING WITH NEW ELECTRICAL CONTRACTOR MEHL ELECTRIC NO LONGER CONTRACTOR-CHANGE CONTRACTOR OF RECORD TO SHOW NEW ON PERMIT
2) OBTAIN APPROVED PLANS WITH LATEST REVISIONS
3) SEE NOTES PREVIOUS INSPECTION 4/16/10 FOR CORRECTION OF EQUIPMENT INSTALLED UNDER PREVIOUS CONTRACTOR
12/02/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COULD NOT LOCATE CONTRACTOR-NO MSG
2) CONTRACTOR OF RECORD TO BE ON PERMIT
3) NOTE: NEW MH PEDESTAL ARE IN USE PRIOR TO INSPECTION APPROVAL. SEE NOTES FOR PROPER USE OF LISTED EQUIPMENT
04/16/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSPECTION FOR M3 SERVICE, CORRECTIONS AS FOLLOWS:
1) FUSES NOT PER PLAN IN MAIN SERVICE DISCONNECT
2) EQUIPMENT GROUNDS SHOULD BE #3 CU PER 250.122 NEC
3) GROUND RODS NOT 10' APART AS SPECIFIED ON PLAN REF. 2006 IBC 106.3.1 AND 106.4
4) SUPPLY CONDUCTORS NOT PER PLAN, ALSO CONDUIT SIZE
5) CIRCUIT BREAKERS NOT RATED 22K PER PLAN
6) KO SEALS NEED TO BE LISTED FOR OUTDOOR USE AND APPLICATION
7) SERVICE DISCONNECT NOT RATED PER PLAN (200K) ?
8) SECURE GROUND ELECTRODE CONDUCTOR TO ENCLOSURE
MC SERVICE DISCONNECT AND REMOTE PANEL:
1) CONDUIT REDUCING WASHER AT BOTTOM OF MAIN DISCONNECT NOT LISTED TYPE
2) NOTES #1,2,3,4,7 & 8 FROM 'M3' INSPECTION APPLICABLE TO 'M2' SERVICE
3) EXPOSED CONDUITS TO GALV. IMC PER PLAN
M1 SERVICE:
1) NOTES FROM 'M3' INSPECTION APPLY #1,4,5,7 & 8
PEDESTAL INSPECTION TYPE OF 13:
1) NOT INSTALLED PER LISTING-SERVICE EQUIPMENT ONLY 110.3 NEC
2) NO BUSHING ON CONDUITY ENTRY INTO PEDESTAL 300.5-H AND 352.46
3) NEUTRAL AND EQUIPMENT GROUND TIED TOGETHER IN PEDESTAL 250.6
4) ILLEGAL DBL TAPING ON SUPPLY SIDE OF PEDESTAL
5) VERIFY SPLICES LISTED FOR WET LOCATION 314.30 NEC
6) DEVICES (RECEPTS) 4-WIRE NOT GROUNDED 250 NEC
7) INSTALL PERMANENT ADDRESS OR UNIT LABELS ON PEDESTALL 110.22