Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER DEMO 2) BOND JUMPER TO BE SIZED PER 250.66 AND 250.102 |
|
| 03/19/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT CONDUCTORS 300.4 2) NEED ANTIOXIDE COMPOUND FOR ALUMINUM TERMINATIONS AND SPLICES 3) BOND JUNCTION BOX ENCLOSURE 4) USE APPROVED HUB/FITTING FOR RISER 5) NUMBER OF CONDUCTORS EXCEED WIRE NOT CAPACITY |