Permit: T10EL00554

Parcel: 128111950


Addresses:

4809 E PASEO LUISA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/29/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL
2) USE CORRECT BREAKER SIZED FOR CONDUCTOR AMPACITY-MAIN PANEL
3) NO GROUNDING ELECTRODE SYSTEM AT SERVICE
4) PLEASE VERIFY SERVICE UPGRADE PERMIT ]
5) NO GAS BOND PRESENT
6) GROUNDED RECEPTS ON ALL UNGROUNDED SYSTEM
7) EXPOSED ZIP CORD WIRING TO LIGHT
8) KITCHEN RECEPTS TO BE GFCI PROTECTED
9) EXPOSED NM CABLE FOR HOOD AND AT RANGE
10) PROTECT BULBS IN CLOSETS
11) SMOKE DETECTORS NEEDED IN BEDROOMS-INSTALL PER INSTRUCTIONS
12) EXPOSED CONDUCTORS IN CLOSET ABOVE SUB PANEL
13) COMBUSTION AIR REQUIRED FOR WATER HEATER, PLEASE VERIFY SERVICE AND QUALITY