Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EQUIPMENT GROUND FOR 50 AMP TO 30 AMP CIRCUITS TO BE #10 NEC 250.122 2) CONNECT EQUIPMENT AROUND TO JUNCTION BOX 250.148 3) EQUIPMENT GROUNDING CONDUCTORS AND NEUTRAL CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINOUS ALONG ENTIRE LENGTH 250.119 AND 200.6 4) SEAL OPENING BACK OF JUNCTION BOX WITH NON COMBUSTIBLE MATERIAL 5) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL, SEE PANEL DOOR |
|
| 03/16/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSSOVER-NO LOAD CONNECTED |