Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT CONDUIT WITHIN 3' OF JUNCTION BOX 2) CORRECTLY INSTALL LOCK NUT TO MAINTAIN GROUND FAULT PATH 3) FINISH #1-110.26 WORKING SPACE |
|
| 03/17/2010 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NO WORK PROGRESS |
|
| 03/11/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING SPACE IN FRONT OF PANEL-DRAIN PIPE 2) RECALL AFTER CROSSOVER |