Permit: T10EL00481

Parcel: 131090450

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/17/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1 - COMPLETE ITEMS 8, 10, 12 FROM PREVIOUS INSPECTION
2 - VERIFY PERMIT FOR SHOP STORAGE BUILDING ON PROPERTY
06/15/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) LOCKED, NO ACCESS
2) COULD NOT UNDERSTAND MESSAGE
03/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1. HAVE CUT IN DOORWAY WITH ROMEX RUNNING THROUGH IT
2. INSTALL JUNCTION BOXES @ SPLICE CONNECTIONS
3. INSTALL MISSING WALL PLATES
4. KITCHEN COUNTER RECEPTACLES TO BE GFCI PROTECTED
5. HAVE EXPOSED WIRING @ CEILING BOXES
6. INSTALL SMOKE DETECTORS IN BEDROOMS & OUTSIDE OF BEDROOMS
7. HAVE BROKEN RECEPTACLES
8. CLOTHES CLOSET LIGHTS BE 100% ENCLOSED
9. ROOF TOP UNIT APPEARS TO BE IN DISREPAIR, MISSING COVERS, ETC.
10. OUTDOOR RECEPTACLES TO BE GFCI PROTECTED & HAVE WEATHERPROOF COVERS
11. HAVE OPEN BOX @ SERVICE WITH DAMAGED CABLES
12. OPEN BACK BUILDING FOR INSPECTION
13. HAVE QUALIFIED ELECTRICAL CONTRACTOR GO THROUGH HOME AND MAKE REPAIRS AND CHECK WIRING