Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 03/05/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OUTSIDE RECEPTACLE ON N SIDE OF HOUSE NEEDS TO BE GFCI PROTECTED & IN WATERPROOF BOX & COVER. 2. KITCHEN COUNTER & BATHROOM RECEPTACLES NEED TO BE GFCI PROTECTED. 3. INSTALL SMOKE DETECTORS IN HALLWAYS & BEDROOMS, ALSO COVER PLATES MISSING OFF LIGHT SWITCHES & RECEPTACLES. 4. CORD CONNECTED WATER HEATER, NEEDS TO BE HARD WIRED WITH DISCONNECT SWITCH 5. CIRCUIT BREAKERS IN SERVICE PANEL NEED TO MATCH MFR OF PANEL, INSTALL BLANKS 6. COOLER WIRING NOT CODE - CORRECT 7. ELECTRICAL J-BOX IN BACK OF HOUSE, PULLED OFF WALL - USE LICENSED OR QUALIFIED ELECTRICIAN. |