Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/04/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 2) INSTALL MISSING WALL PLATES 3) BATHROOM RECEPTS TO BE GFI PROTECTED 4) INSTALL SMOKE DETECTORS 3' FROM VENTS IN BEDROOMS 5) HOME MISSING FURNACE, NEED TO OBTAIN PERMIT FOR NEW FURNACE 6) CONDUCTORS HANGING AT CONDENSING UNIT LOCATION NEED TO BE REMOVED OR INSTALLED IN JUNCTION BOX 7) HAVE #8 ROMEX AT SERVICE PANEL ON 60 AMP BREAKER FEEDING SUB PANEL NOT PROPERLY PROTECTED, NEED #6 CONDUCTORS OR TO BE REMOVED 8) RESCHEDULE WHEN COMPLETE |