Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BOND GAS AND WATER PIPING TO SERVICE PANEL 2) PANEL NOT DESIGNED OR LISTED FOR SPLIT BREAKERS TO BE INSTALLED. SPLIT BREAKERS THAT ARE INSTALLED HAVE BEEN BROKEN/ALTERED TO GET THEM TO FIT INTO PANEL 3) PROPERLY SEAL AND WATER PROOF ALL PENETRATIONS THRU ROOF 4) RECALL AFTER SWING OVER IS COMPLETE |
|
| 02/25/2010 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) MEETING TO DISCUSS PROJECT |