Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10EL00403

Parcel: 12218122E


Addresses:

1416 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/05/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/02/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GEC SPLICE NEEDS TO BE IRREVERSIBLE CRIMP OR CADWELD, ALSO MUST BE SUPPORTED TO STRUCTURE
2) CONDUCTOR NEEDS TO BE SAME SIZE AS EXISTING