Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE REVISE DIRECTORY PANEL L-1 2) CIRCUITS NOT PER PLANS 3) NEED FIXTURE DISCONNECTING MEANS 410.73 (G) 4) PLANS CALL NOT PERMITTED M/C CABLE |