Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ITEMS ON LIST ALL OK |
|
| 02/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECEPTS HANGING OUT OF WALLS 2) MISSING WALL PLATES 3) GFI RECEPTS INSTALLED ARE FOR COPPER CONDUCTORS ONLY 4) CLOSET LIGHT TO BE 100 PERCENT ENCLOSED 5) BLANK OPEN BREAKER POSITION IN PANEL 6) NEED PANEL DIRECTORY 7) RESCHEDULE WHEN COMPLETE |