Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2010 | ELECTRIC - FINAL | Approved | ||
| 02/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. EXPOSE GROUND RODS AT SHOP BUILDING 2. HAVE BROUNDED RECEPTACLES IN SHOP, NO GROUND RUN TO BUILDING FROM SERVICE, INSTALL GFCI RECEPTACLES AHEAD OF RECEPTACLE CIRCUIT OR CHANGE GROUNDED RECEPTACLES TO 2 WIRE TYPE. 3. CONNECT NEUTRAL BAR TO ENCLOSURE PER NEC 250.32 USE QUALIFIED OR LICENSED ELECTRICIAN FOR THE WORK |
|
| 02/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COOLER BOX ON ROOF NEEDS TO BE SUPPORTED 2) GOUNDING ELECTRODE CONDUCTOR TO SHOP IN BACK HAS BEEN CUT.; RE-GROUND PER 250.32 3) HAS STRUCTURAL DAMAGE TO ROOF NEC 4) INSTALL SMOKE DETECTORS IN BEDROOMS |