Permit: T10EL00297

Parcel: 122173970


Addresses:

3144 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/03/2010 ELECTRIC - FINAL Approved
02/22/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1. EXPOSE GROUND RODS AT SHOP BUILDING
2. HAVE BROUNDED RECEPTACLES IN SHOP, NO GROUND RUN TO BUILDING FROM SERVICE, INSTALL GFCI RECEPTACLES AHEAD OF RECEPTACLE CIRCUIT OR CHANGE GROUNDED RECEPTACLES TO 2 WIRE TYPE.
3. CONNECT NEUTRAL BAR TO ENCLOSURE PER NEC 250.32

USE QUALIFIED OR LICENSED ELECTRICIAN FOR THE WORK
02/12/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COOLER BOX ON ROOF NEEDS TO BE SUPPORTED
2) GOUNDING ELECTRODE CONDUCTOR TO SHOP IN BACK HAS BEEN CUT.; RE-GROUND PER 250.32
3) HAS STRUCTURAL DAMAGE TO ROOF NEC
4) INSTALL SMOKE DETECTORS IN BEDROOMS