Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00282
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/21/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OFFICE CLOSED 2) PLEASE CORRECT CONTRACTOR OF RECORD (NOT MEHL) 3) RESCHEDULE INSPECTION AND HAVE CONTRACTOR ON SITE TO WALK THRU JOB. ALSO HAVE APPROVED PLANS AND PERMITS 4) SEE IMPORTANT NOTICE ON YELLOW PERMIT CARD FOR INSPECTION HOURS |
|
| 10/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE APPROVED PLAND FOR U.G. AND ABOVE GROUND WIRING FOR 22 COACH LIGHT INSTALL, INCLUDE PULL BOXES AND LOCATIONS, CIRCUIT DESIGNATION, LOAD CALCS 2) WALKED JOB WITH LARRY MEHL AND HIS ELECTRICIAN TO INSPECT WORK AS INSTALLED CODE VIOLATIONS AS FOLLOWS: 1) PULL BOX AT WEST PARKING LOT HAS SETTLED BELOW GRADE, METAL COVER NEEDS TO BE GROUNDED PER 250 NEC. ALL SPLICES TO BE RATED FOR WET LOCATION. UF SHEATH TO BE ABOVE GRADE INSIDE PULL BOX 110.2 NEC 2) PROVIDE MANUFACTURE OF COACH LIGHT INSTALLATION INSTRUCTIONS/OR VERIFY BURRIAL DEPTH OF POLE 110.3 NEC METAL POLES TO BE GROUNDED PER 250 NEC. PROVIDE BUSHINGS AT PVC OR OTHER CONDUIT TERMINATIONS IN PULL BOXES 3) POT HOLE CONDUITS INSTALLED BY CONTRACTOR COMPLY WITH 300.5 NEC AT PULL BOXES AND COACH LIGHTS 4) RECALL INSPECTION WHEN DONE |
|
| 10/04/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER MANDI BATES, WILL RESCHEDULE |
|
| 10/01/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVIEWED SCOPE OF WORK WITH MANAGER 2) CONTRACTOR TO SHOW-U.G. WIRING, PULL BOXES THRU OUT SITE 3) NO INSPECTIONS, ALL COVERED 4) SOME COACH LIGHTS ARE FALLING OVER-ADVISED MANAGER NOT TO USE DUE TO POSSIBLE LIFE SAFETY 5) NO PLANS, CALLED CONTRACTOR WITH ETA PER REQUEST 9:10 AM NOW AND CALLED AT 8:25 AM |
|
| 08/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) CONTRACTOR NO SHOW 2) A REINSPECTION FEE IS ASSESED, THIS IS THE 5TH ATTEMPT, CALLED PHONE NUMBER (MEHL ELECTRIC) PER REQUEST AND LEFT MSG. WITH ETA ON TONY'S CELL PHONE. LEFT MESSAGE AT 7:40 AM-TIME NOW 8:44 AM. PAY REFEE PRIOR TO NEXT INSPECTION 201 N. STONE |
|
| 07/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) LEFT 2 MESSAGES AND NO ONE ON SITE 2) RESCHEDULE WITH DAN |
|
| 07/09/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL BACK FOR REINSPECTION |
|
| 06/17/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/02/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT CONTRACTOR OF RECORD 2) HAVE CONTRACTOR ON SITE TO OPEN EQUIPMENT AS NECESSARY |