Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999$ 1) NEED BOND PANEL, WEATHER PROOF BOX AND GUTTER AT SERVICE 250.98-A 2) NEED TO TIGHTEN LB TO PANEL AND NEED PANEL SCHEDULE 3) NEED TO USE CLOSE NIPPLE OR LOCK NUT ON LB TO GUTTER NOT JUST A CHASE NIPPLE 250.98-A2 4) NEED TO LOOK INSIDE OF BLDG AND LEAVE CONTACT NUMBER |
|
| 04/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECTIONS NOT DONE THERE MAYBE A REFEE ON NEXT INSPECTION |
|
| 02/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) NEED K.O. SEALS FOR SIDE & BOTTOM OF DISCONNECT AT SERVICE TO MAIN DISCONNECT CANNOT HAVE 2 WIRES ON 1 LUG 2) NEED TO WIRE, NUT WIRES TO BACK OF BLDG 3) NEED SERVICE TO BE 12' NOT 9' 4) NO ACCESS TO BLDG |