Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/18/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOW IS NEW GROUNDING SYSTEM TIED INTO NEW SERVICE ? 2) INSTALL PERMANENT ADDRESS LABEL ON SERVICE 3) VERIFY WATER AND GAS PIPING BONDED 4) GROUNDING ELECTRODE CONDUCTOR MUST BE UN-SPLICED PER 250 NEC 5) VERIFY BRANCH WIRING NOT EXPOSED BEHIND PANEL |