Permit: T10EL00261

Parcel: 117032300


Addresses:

722 N 10TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/19/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/18/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOW IS NEW GROUNDING SYSTEM TIED INTO NEW SERVICE ?
2) INSTALL PERMANENT ADDRESS LABEL ON SERVICE
3) VERIFY WATER AND GAS PIPING BONDED
4) GROUNDING ELECTRODE CONDUCTOR MUST BE UN-SPLICED PER 250 NEC
5) VERIFY BRANCH WIRING NOT EXPOSED BEHIND PANEL