Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00226
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
02/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 2/0 BOND JUMPERS ON SUPPLY SIDE OF SERVICE DISCONNECT CT - TO GUTTER PER 250 - 66 BOND BUSHINGS LINE SIDE OF DISCONNECTS #4 - PERMANENT LABELS ON EQUIP - BOND BUSHINGS ON SECONDARY STEEL CONDUITS - BOND SCREWS IN DISCONNECTS. (NEUTRAL) |
|
01/26/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RE-INSP FEE NEXT INSPECTION-NO ONE ON SITE AND PANELS LOCKED |
|
01/24/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* plans/permit equip. to be opened for insp expose ground rods bonding conectors ahead of disconnects per 250-66 nec |