Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO OBTAIN PERMIT FOR NEW FURNACE, FURNACE HAS BEEN REMOVED 2) HOUSE GROUNDED RECEPTS ON 2 WIRE UNDERGROUND SYSTEM 3) REVISE HOUSE PERMIT FOR PANEL REPLACEMENT, PANEL LOCKED AND NO ACCESS |
|
| 03/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) HOUSE LOCKED AND NO ACCESS 2) LEAVE MESSAGE WITH ACCESS DIRECTIONS |
|
| 02/04/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MISSING WALL PLATES 2) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED 3) BLANK OPEN BREAKER POSITION PANEL IN MECHANICAL CLOSET 4) NEED PROPER CLEARANCE TO GRADE ON OVERHEAD FEEDER TO CARPORT/SHED 5) RECEPTS AT CARPORT/SHED TO BE GFI PROTECTED 6) BATHROOM RECEPT TO BE GFI PROTECTED 7) INSTALL SMOKE DETECTOR IN BEDROOMS PER INSTRUCTIONS 8) HAVE EXPOSED WIRES AT CONDENSING UNIT LOCATION-UNIT HAS BEEN REMOVED 9) MISSING FURNACE UNIT HAS BEEN REMOVED, NEED TO INSTALL NEW UNIT AND OBTAIN PERMIT 10) HAVE GROUNDING TYPE RECEPTS ON UNGROUNDED SYSTEM 11) HAVE NON-CODE COMPLIANT TAPS AT SERVICE 12) SERVICE SHOULD BE UPGRADED 13) CLOTHES CLOSET LIGHTS TO BE 100 PERCENT ENCLOSED 14) EXPOSED WIRING AT RANGE LOCATION. RECEPT HAS BEEN REMOVED 15) HAZARDOUS-NO RECONNECT |