Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00207
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2010 | ELECTRIC - FINAL | Partial Approval | NEED INSPECTION OF FURNACE | |
02/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY PERMIT FOR INSTALLED FURNACE |
|
02/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS ON BLDG 2) KITCHEN RECEPTS TO BE GFCI PROTECTED 3) BATHROOM RECEPT TO BE GFCI NOT A SWITCH 4) MISSING COOLER SWITCH COVER PLATE 5) NEED SMOKE DETECTORS IN BEDROOMS 6) GROUND NEW SWITCHES 7) MISSING LIGHT FIXTURE LAUNDRY ROOM 8) EXPOSED AND HANGING NM CABLE & CONDUCTORS 9) 1/2" EMP CONDUIT ACCROSS ROOF AND TO PANEL NOT INSTALLED TO CODE 10) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 11) LABEL SERVICE-A PERMANENT METAL ADDRESS LABEL 12) MISSING FURNACE 13) NO QUICK RELEASE FOR WROUGHT IRON BARS-NO RELEASE AT ALL 14) UNIT IS NOT HABITABLE |