Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/24/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MIN 6' APART. 2) HAVE INDIVIDUAL CONDUCTORS RUNNING UP WALL INTO ATTIC SPACE. NEEDS TO BE INSTALLED IN CABLE ASSEMBLY OR RACEWAY. APEX CONDUCTORS NOT RECOGNIZED WIRING METHOD 3) OLD CABLE (SEU) APPEARS TO BE 60 AMP RATED NOT 100. |