Permit: T10EL00165

Parcel: 120071640


Addresses:

210 W PALMDALE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/02/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/27/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN LOOSE LINE SIDE CONNECTIONS
2) CLEAN SURFACE FOR GAS BOND CLAMP
3) FILL UNUSED OPENING BACK OF JUNCTION BOX
4) SHEET METAL THREADED SCREWS NOT ALLOWED FOR GROUNDING
5) CLEAN SURFACE UNDER GROUND LUG
6) CONNECTORS NEEDED FOR CABLES ENTERING JUNCTION BOX
7) PROPERLY INSTALL FITTINGS AND BUSHINGS AT MAIN PANEL & JUNCTION BOX