Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/27/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TIGHTEN LOOSE LINE SIDE CONNECTIONS 2) CLEAN SURFACE FOR GAS BOND CLAMP 3) FILL UNUSED OPENING BACK OF JUNCTION BOX 4) SHEET METAL THREADED SCREWS NOT ALLOWED FOR GROUNDING 5) CLEAN SURFACE UNDER GROUND LUG 6) CONNECTORS NEEDED FOR CABLES ENTERING JUNCTION BOX 7) PROPERLY INSTALL FITTINGS AND BUSHINGS AT MAIN PANEL & JUNCTION BOX |