Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 02/02/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDUCTORS AND CABLE ENTERING BACK OF JUNCTION BOX TO HAVE A CONNECTOR 2) GROUND JUNCTION BOXES |
|
| 01/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN RECEPTS TO BE GFCI PROTECTED 2) SMOKE DETECTORS NEEDED IN BEDROOM-INSTALL PER INSTRUCTIONS 3) WIRING AND BOX AT SIDE OF PANL TO BE FOR WET LOCATION 4) MISSING GROUNDING ELECTRODE SYSTEM, ALSO GAS AND WATER BOND 5) SUPPORT RISER ABOVE METER 6) COOLER WIRING NOT FOR WET LOCATION ON ROOF 7) PLEASE HAVE QUALIFIED ELECTRICIAN PERFORM WORK |