Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED CHECK #9866 FOR $150.00 FOR SATURDAY INSPECTION |
|
| 02/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO SEE INTO TERM CAN. AND GUTTER 2) SHOULDER OF 4" CONNECTOR INTO TERM CAN TO BE SEATED AGAINST CAN 3) MARK DISCONNECT WITH PANEL SERVED 4) NEED TO HAVE POWER TO GET FINAL 5) FLEX TO BE PROTECTED FROM PHYSICAL DAMAGE WHERE RUN ACROSS FLOOR |