Permit: T10EL00089

Parcel: 12007338B


Addresses:

351 W PRESIDENT ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/20/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) POST ADDRESS ON BLDG
2) GROUNDED RECEPTS ON UNGROUNDED CIRCUITS
3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE
4) A CONNECTOR IS NEEDED AT HOOD
5) SWITCH BROKEN
6) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
7) PROTECT CABLE ENTERING PANEL FROM SHARP METAL EDGES
8) PROPERLY SUPPORT COOLER WIRING
9) WHAT IS NM CABLE PARTIALY BURIED BY WATER HEATER FOR ?