Permit: T10EL00086

Parcel: 135072920


Addresses:

1319 S MARC DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL00086

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/02/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMIT ISSUED IS FOR FEEDER AND SUB-PANEL ONLY. NEED TO REVISE PERMIT AND PROVIDE PLANS FOR ALL NEW ELECTRICAL INSTALLED IN SHED
2) ALL ELECTRIC IN SHED COVERED WITHOUT INSPECTIONS
3) NEED TO OBSERVE ALL NEW WORK
4) SHOULDE PROVIDE LOAD CALCULATIONS FOR ADDING NE LOAD TO 100 AM SERVICE 0 HOME
5) INSTALL BREAKERS LISTED FOR USE IN GE SERVICE PANEL
6) EXPOSE GROUNDING ELECTRODE SYSTEM AT NEW STRUCTURE
7) NEED MAIN DISCONNECT AT SHED NEC 225.32 & 225.33