Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/19/2010 | ELECTRIC - FINAL | Denied | 1) GROUNDED RECEPTS ON UNGROUNDED CIRCUITS 2) KITCHEN RECEPTS TO BE GFCI PROTECTED 3) BATHROOM RECEPT TO BE GFCI PROTECTED 4) INSTALL SMOKE DETECTORS 7"-9" DOWN FROM CEILING 5) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS AT PANEL EXTERIOR 6) SEAL ENTRANCE AT TOP OF PANEL WITH AN APPROVED FITTING 7) USE APPROVED TERMINAL CONNECTIONS AT PANEL INTERIOR |