Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ITEMS ON LIST ALL OK |
|
| 01/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED WIRING METHODS FOR BALANCER AND TIRE MACHINES COMPRESSORS: 1) SUPPORT CONDUIT UP WALLS 2) ONLY ONE CONDUCTOR PER LUG 3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4) OVER CURRENT PROTECTION NOT PER LISTING LABEL 5) MAINTAIN WORKING CLEARANCES 110.26 |