Permit: T10EL00002

Parcel: 120076490


Addresses:

519 W AJO WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) ITEMS ON LIST ALL OK
01/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED WIRING METHODS FOR BALANCER AND TIRE MACHINES
COMPRESSORS:
1) SUPPORT CONDUIT UP WALLS
2) ONLY ONE CONDUCTOR PER LUG
3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
4) OVER CURRENT PROTECTION NOT PER LISTING LABEL
5) MAINTAIN WORKING CLEARANCES 110.26