Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/08/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER SWING OVER COMPLETE |
|
| 01/06/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIMUM 6' APART 2) SERVICE CONDUCTORS TO BE MARKED SUN LIGHT RESISTANT 3) MINIMUM POINT OF ATTACHMENT TO BE 10' AND NEED MINIMUM 12' OF CLEARANCE OVER RESIDENTIAL PROPERTIES |