Permit: T10EL00001

Parcel: 126133950


Addresses:

4618 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/20/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/08/2010 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RECALL AFTER SWING OVER COMPLETE
01/06/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS TO BE MINIMUM 6' APART
2) SERVICE CONDUCTORS TO BE MARKED SUN LIGHT RESISTANT
3) MINIMUM POINT OF ATTACHMENT TO BE 10' AND NEED MINIMUM 12' OF CLEARANCE OVER RESIDENTIAL PROPERTIES