Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2010 | INSP - INITIAL CODE ENFORCMENT | Approved | INSPECTION RESULTS AS FOLLOWS: MET TENANT ON SITE, THE REAR UNIT HAS NO PERMANENT SOURCE OF HEAT, NO FLOOR COVERING FOR THE ENTIRE INTERIOR AND NO SMOKE DETECTORS. THREE METAL TYPE JUNCTION BOXES WITH METAL CLAD CABLE HAS BEEN INSTALLED IN THE INTERIOR OF THE LIVING / BEDROOM AREA. THE MC CABLE IS ABOUT 12 TO 18 INCHES FROM THE FINISH FLOOR AND SUBJECT TO PHYSICAL DAMAGE. THIS CONTINUATION OF THE LIVING OUTLET WAS DONE WITHOUT A PERMIT. THE EXTERIOR PANEL HAS MC FROM A 20 AMP BREAKER GOING UP THE WALL AND OVER THE ROOF. SUB PANEL HAS NO GROUND CONNECTION TO THE SERVICE EQUIPMENT, EQUIPMENT GROUNDS AND NEUTRALS CONNECTED TOGETHER IN THE INTERIOR OF THE SUB PANEL. MIS-IDENTIFIED EQUIPMENT GROUNDING CONDUCTORS AND MISIDENTIFIED NEUTRAL CONDUCTORS. |