Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T10DV05368
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2010 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CALL OUT FROM TFD ON SITE INSPECTION RESULTS WERE AS FOLLOWS: THE DWELLING IS A MANUFACTURE HOME, ELECTRICAL FIRE IN THE WALL MELTED THE OUTLET ALONG WITH THE DUPLEX RECEPTACLE AND CONDUCTORS TO THE OUTLET. THERE ARE BURNT EXPOSED WIRES IN THIS AREA. TEP DID REMOVE THE METER. THERE WAS A WINDOW MOUNT AIR CONDITIONING UNIT THAT WAS PLUGGED INTO A 16 INCH EXTENSION CORD THAT WAS PLUGGED INTO THE OUTLET. THE A/C UNITS DATA PLATE READ THE UNIT WAS A 12 AMP 1410 WATTS 15100 BTU, 115VOLT/60HZ/1PH. TWO WALL STUDS WERE SEVERELY CHARRED MORE DAMAGED WAS DONE TO THE ADJACENT WALL STUDS, WALL SHEATHING, INSULATION AND THE INTERIOR WALL. PERMITS ARE REQUIRED FOR THE REPAIRS TO THE ELECTRICAL AND STRUCTURAL DAMAGE. SCHEDULED FOLLOW UP INSPECTION FOR 60 DAYS OUT. |