Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2010 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CALL OUT BY TPD, TO DUPLEX 2107 MINIMUM HOUSING ISSUES; BATHROOM SHOWER COMPARTMENT WALLS ARE UNFINISHED WITH EXPOSED WALL STUDS, THERE IS A CABLE RUNNING THROUGH THE STUDS AND ONE OUTLET ABOVE THE SHOWER VALVES. THERE IS PLASTIC TAPED IN THE AREA. THE TENANTS STATED IT HAS BEEN IN THAT CONDITION SINCE FEB, 2010. THE TUB IS UNSTABLE. THE INTERIOR OF THE DWELLING HAS DRYWALL DAMAGE IN THE BEDROOM CLOSET AREA AND LIVING ROOM. THE BEDROOM HAS A MISSING REGISTER. THE KITCHEN SINK FAUCET IS BROKEN, MISSING COVER PLATE ON OUTLET BACK SPLASH AREA. NO SMOKE DETECTORS. THERE IS A GAS FIRED WATER HEATER LOCATED UNDER THE EAVE AREA IN THE BACKYARD. THE UNIT IS OUTDOORS WITH NO PROTECTIVE ENCLOSURE. THERE IS AN ADDED PANEL BROAD WITH A 20 AMP BREAKER AND JUNCTION BOX BELOW THE PANEL BOARD LOCATED DOWNSTREAM FROM MAIN DISCONNECT WHICH WAS INSTALLED WITH OUT PERMITS. THE PROPERTY HAS WEEDS THAT EXCEED 6 INCHES IN HEIGHT, WITH TRASH AND DEBRIS, LITER. UNIT 2105 ELECTRIC WATER HEATER INSTALLED WITHOUT A PERMIT, THE UNIT IS LOCATED IN THE BACKYARD UNDER EAVE AREA. THE UNIT IS OUTDOORS WITH NO PROTECTIVE ENCLOSURE. THE UNIT IS POWERED WITH A BLACK CABLE FROM THE DISCONNECT WHICH RUNS ABOVE GROUND ON GRADE ALONG THE BUILDING. THIS CABLE IS NOT RATED FOR OUTDOOR USE. THIS CIRCUIT WAS INSTALLED WITHOUT PERMITS. THE WATER HEATER HAS NO DISCHARGE PIPE. THE FRONT HOSE BIB IS DRIPPING WATER. CASE WILL BE ASSIGNED TO AREA INSPECTOR, NOTICE OF VIOLATION TO ISSUED FORTHWITH |