Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T10DV02498
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2010 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE, TENANTS MENTIONED OWNER HAVE BEEN NOTIFIED OF PLUMBING AND ELECTRICAL ISSUES. PLUMBING ISSUES HAVE BEEN ABATED, AND I FOUND NO LEAKY OR BACKED UP PLUMBING. TENANTS MENTIONED THEY HAVE BEEN ISSUED AN EVICTION NOTICE AND MUST BE OUT MAY 31ST.ELECTRICAL HOWEVER HAS NOT BEEN ABATED AND I FOUND THE FOLLOWING ISSUES: >EXPOSED WIRING IN REAR BEDROOM FROM OUTLETS TO LIGHTS, TO SWITCHES. >EXPOSED LIVE WIRE RUNNING THRU DROPPED CEILING GOING TO NOTHING, ONLY ELECTRICAL TAPE TO AVOID SHOCKS. WIRE RUNNING THRU DROPPED CEILING IN KITCHEN NOT PROPERLY SECURED TO RAFTERS. >KITHCEN LIGHT SWITCH NOT WORKING PROPERLY. >EXPOSED WIRING AT LIGHTS AND CEILING FANS IN THE LIVING ROOM >INTERIOR SUB PANEL HAS BEEN ADDED TO THE EXTERIOR, IS DOUBLE LUGGED, AND HAS ADDED CIRCUITS. |