Case: T10DV00335

Parcel: 124050350


Addresses:

744 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/25/2010 INSP - INITIAL CODE ENFORCMENT Approved MET WITH TENANT AND SUPERVISOR ON SITE, TENANT CONCERNS WERE THE CONSTANT BLOWING OF THE FUSES IN THE ELECTRICAL DISCONNECT. THE FUSE IN THE DISCONNECT IS A 30 AMP FUSE.
THERE ARE GROUNDED OUTLETS IN A TWO WIRE SYSTEM.

WE CONDUCTED A BASIC LOAD CALCULATION AND A SURVEY OF ALL APPLIANCES AND SERVICE.

THE SERVICE IS AN OLD 30 AMP FUSE TYPE SYSTEM

SURVEY OF APPLIANCES IN THE UNIT WERE AS FOLLOWS:
(1) ONE PORTABLE ELECTRICAL SPACE HEATERS
(2) TWO A/C WINDOW MOUNT UNITS
(3) ONE COOLER
(4) ONE MICROWAVE

THE EXISTING ELECTRICAL SYSTEM DOES MEET THE CURRENT LOAD DEMANDS OF ALL ELECTRICAL APPLIANCES. WILL HAVE CALCULATION REVIEWED BY DSD ELECTRICAL INSPECTOR. THE TENANT WAS ASKED NOT TO USE THE SPACE HEATERS.

GAS WATER HEATER HAS NO COLD WATER SHUT OFF, HAS PVC BEING USED FOR AS A DISCHARGE PIPE. INSTALL WAS DONE WITHOUT A PERMIT.

THE DWELLING ORIGINAL HEAT SYSTEM WAS REMOVED.