Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP IN THE CONDENSATE DRAIN LINE 2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 3) DISCONNECT FOR MINI SPLIT CONDENSOR WIRED INCORRECTLY, LINE AND LOAD AS SWITCHED 4) A GFI SERVICE RECEPT IS REQUIRED AT THE MINI SPLIT CONDENSOR AND AT CONDENSOR ON ROOF. USE A BUBBLE TYPE WATER PROOF COVER 5) SEAL DUCT AT CONNECTION TO COIL |