Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM03545
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/08/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/29/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOND GUTTERS 250.148 |
|
| 06/24/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CONDUIT RUNS ABOVE CLASS ROOMS 2) SEPERATE GROUNDS AND NEUTRALS 250.24 (C) 3) DO CONDUCTORS HAVE AMBIENT CORRECTIONS CALCULATED IN TO RUN 310.16 4) NEED BELL ENDS |