Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM03529
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/19/2011 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR NOT ON SITE |
|
08/17/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) EXHAUST ISSUES WILL BE LOOKED AT ON FINAL |
|
08/10/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BATHROOM EXHAUST MUST RUN CONTINOUSLY. SEE ENGINEER FOR DIRECTION 2) INSULATE ALL SUPPLY DUCTING ABOVE T-BAR CEILING 3) PROVIDE BEADED COLLARS AT CEILING DIFFUSERS AND PANDUIT STAPS REQUIRED AT FLEX DUCT CONNECTIONS 4) PROGRAM T-STATS FOR A/C FAN TO RUN CONTINOUSLY |