Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH #6,7 & 8 |
|
| 06/13/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND RISER 2) SECURE GROUNDING ELECTRODE CONDUCTOR AND VERIFY GROUND RODS 3) TIGHTEN LOOSE CONDUCTOR TERMINATIONS 4) CANNOT STACK LUGS 5) FINISH PREVIOUS MARKED ITEMS |
|
| 06/01/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORK CLEARANCES 2) FILL UUSED OPENINGS 3) BELL END NEEDED PER 352.46 AND 300.4 4) NEED SURFACE CONTACT FOR GROUND LUGS 5) FINISH SERVICE 6) PLEASE VERIFY BORED RUN FOR SECONDARY 7) VERIFY LISTING OF RACEWAY 8) HDPE TO BE LISTED 353.6 |