Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) #4 AND LARGER CONDUCTORS REQUIRE INS. BUSHING AT TERMINATIONS |
|
| 06/02/2011 | ELECTRIC - ABOVE CEILING | Denied | 1) SUPPORT CONDUIT 3/4" FOR VACUUM SYSTEM AS NOTED ON LAST INSPECTION 2) AIR HANDLER IN LABELING ROOM DISCONNECT SW. POWER TO SWITCH FIRST, LOCK OUT AT CIRCUIT BREAKER 3) CONTRACTOR REQUESTED AFTER HOURS INSPECTION-PAID $165.00 AT PERMIT COUNTER WITH CREDIT CARD 4) SUPPORT 1 1/4" AC CONDUITS OVER CASHIER/CHECKOUT AREA |
|
| 05/31/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUPPORT LV CABLING TO STRUCTURE OR APPROVED HANGERS MC CABLE CONDUIT TO BE SUPPORTED PER CODE AND OFF CEILING GRID DISC SW ON AIR HADNER TO BE ENERGIZED CONDUCTORS PRIOR UNIT |
|
| 05/10/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) OK BELOW SLAB FOR DISPLAY POWER IN ELECTRONIC AREA |