Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T10CM03492
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
07/07/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) COMPLETE GREASE DUCT FIRE WRAP 2) PROVIDE AIR BALANCE REPORT 3) PROVIDE DUCT SMOKE DETECTOR WITH AUDIO/VISUAL ALARM 4) MECH. CONTRACTOR TO BE ON SITE FOR DUCT SMOKE DETECTOR TEST, HOOD TESTING AND SMOKE CONTAINMENT; ETC...... |
|
06/03/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
06/02/2011 | MECHANICAL - HOODS | Partial Approval | 1) SMOKE/LEAK TEST ON TYPE I DUCT OK, OK TO FIRE WRAP 2) HVAC DUCT SMOKE DETECTOR IS TO BE MOUNTED UPSTREAM OF OUTSIDE AIR INTLET AND PER MANUFACTURES INSTALLATION INSTRUCTIONS |
|
06/01/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) SMOKE/LEAK TEST FAILED |
|
04/13/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST 12' DROP SMOKE LEAK TEST OK, OK TO SINGLE LAYER FIRE WRAP 12' AND DBL LAYER 4' |