Permit: T10CM03492

Parcel: 10707003H


Addresses:

2727 N FAIRVIEW AV


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T10CM03492

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2011 MECHANICAL - HOODS Approved IVRS - Inspection :*
07/07/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) COMPLETE GREASE DUCT FIRE WRAP
2) PROVIDE AIR BALANCE REPORT
3) PROVIDE DUCT SMOKE DETECTOR WITH AUDIO/VISUAL ALARM
4) MECH. CONTRACTOR TO BE ON SITE FOR DUCT SMOKE DETECTOR TEST, HOOD TESTING AND SMOKE CONTAINMENT; ETC......
06/03/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
06/02/2011 MECHANICAL - HOODS Partial Approval 1) SMOKE/LEAK TEST ON TYPE I DUCT OK, OK TO FIRE WRAP
2) HVAC DUCT SMOKE DETECTOR IS TO BE MOUNTED UPSTREAM OF OUTSIDE AIR INTLET AND PER MANUFACTURES INSTALLATION INSTRUCTIONS
06/01/2011 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) SMOKE/LEAK TEST FAILED
04/13/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST 12' DROP SMOKE LEAK TEST OK, OK TO SINGLE LAYER FIRE WRAP 12' AND DBL LAYER 4'