Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM03485
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2011 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/03/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY LABEL COMBINER PANEL BREAKERS 408.4 2) PLANS SHOW A LINE SIDE TAP-REVISE PLANS OR INSTALL PER PLANS 3) ONLY ONE CONDUCTOR PER LUG TERMINATION 4) TIGHTEN CONDUCTOR TERMINATIONS 5) USE UV RATED TYE WRAPS 6) PROPERLY ERECT LADDER PER OSHA STANDARDS |
|
| 09/30/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |