Permit: T10CM03485

Parcel: 11515067G


Addresses:

2245 N 13TH AV #02


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T10CM03485

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2011 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/03/2011 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROPERLY LABEL COMBINER PANEL BREAKERS 408.4
2) PLANS SHOW A LINE SIDE TAP-REVISE PLANS OR INSTALL PER PLANS
3) ONLY ONE CONDUCTOR PER LUG TERMINATION
4) TIGHTEN CONDUCTOR TERMINATIONS
5) USE UV RATED TYE WRAPS
6) PROPERLY ERECT LADDER PER OSHA STANDARDS
09/30/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*