Permit: T10CM03479

Parcel: 117082680


Addresses:

915 S 4TH AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
02/15/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
1) UNIT #8 NEEDS TRIM AND POWER CHECK
2) OK TO CLEAR ECO/RECN FOR #9 LAUNDRY
02/10/2011 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
02/09/2011 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1. GROUNDING ELECTROD TO BE BONDED TO GROUNDED CONDOCTOR
2. NEED BOND BUSHING ON RISER
3. SPLICIES TO BE ACCESSABLE
02/08/2011 ELECTRIC - UFER Denied IVRS - Inspection :
There is no access to the site.| 920*
01/19/2011 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) OK FEEDERS (NEW) TO SUB PANEL
2) PROVIDE 42K ARC PROTECTION PER PLAN OR CONSULT WITH TEP FOR ARC AT SERVICE
3) CONNECT GROUNDING TO SES