Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2011 | FIRE - ALARM FINAL | Approved | ||
| 10/19/2011 | FIRE - ALARM FINAL | Denied | 1. Page FA2 Stair 4 or maybe 3? No horn/sounder need to install one. 2. Page FA3 Data center, add two more horns/sounders on north wall of the room. Room is to loud for the devices that are installed, need to be 10 dec. above room sounds during operations. 3. 1st floor drive ramp to 2nd floor drive strobes and sounders failed. 4. 5th floor short on sounder line showing on panel, strobe/sounder on wall to stair #1 5. 4th floor family restroom add strobe/sounder 6. 4th floor AOR's not wired to the outside switches. |