Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
| 11/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | FOR LEVELS B1-B3: VFD'S OK. NEED ACCESS PANEL LEVEL B1 AT ELEVATOR NEED TO COMPLETE LIGHTS AT MECH ROOMS FOR FANS NEED TO COMPLETE CAR CHARGERS |
|
| 10/19/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS-VDV CABLING 2) FINISH CONTROL WIRING-VDV 3) LOOSE FITTINGS VDV RACEWAYS |
|
| 10/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECK FIXTURES FOR DISCONNECTING MEANS 410.63 (G) 2) MICROPHONE CABLE LAYING ON GRID 725.8 3) EV CHARGER TO BE INSTALLED PER 625.13 & 625.23 |
|
| 10/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCUSSED ELECTRICAL INSTALLATION METHODS |
|
| 09/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOXES IN COMM ROOMS FOR POWER 314.2 |
|
| 09/23/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY ORANGE ENT(INTER DUCT) LISTING 362.6 |
|
| 09/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK H1E MAIN LUGS 2) OK CONDUITS ON NORTH RACK AT SERVICE DRIVE |
|
| 09/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RECESSED CANS ROOM 242 2) VDV CABLES NOT FINISHED |
|
| 09/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE APPROVED STRAPS FOR M/C CABLE 2) SECURE M/C CABLE 12" + 6' INTERVALS 3) NEED JUNCTION BOX ACCESS |
|
| 09/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CANNOT USE CONNECTORS ON ROUNDS IN BOXES 314.2 2) VERIFY BOX FILL ON 4 SQUARE, RWG AND 4/0 PANCAKES 3) PLEASE VERIFY TYPE OF FIRE ALARM CABLES TO APPLY 4) APPLICABLE CODES |
|
| 09/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GENERAL WALK THRU AND ANSWERED QUESTIONS 2) SPOKE WITH CLIMATEC ABOUT 10' SUPPORTS ON DVDE CABLING PER ENGINEER OF RECORD |
|
| 09/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR: 1) NEED JUNCTION BOX ACCESS 2) NO MORE THAN 360 DEGREE IN CONDUIT RUNS (POWER AND DATA) 3) PROTECT VDV CABLES FROM SHARP METAL EDGES |
|
| 09/06/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 9TH FLOOR: 1) OK 2 X 4 LAY IN'S OFFICES 9TH FLOOR 2) OK 9TH FLOOR PATIO 3) NEED ACCESS TO JUNCTION BOXES 4) SECURE M/C CABLES WITHIN 12" OF BOXES 5) MISSING JUNCTION BOX AND ? COVERS 6) PROTECT VDV FROM SHARP METAL EDGES 7) SUPPOR VDV CABLES 725.24 AND 300.11 |
|
| 08/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 08/25/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILING FANS & POWER ROOM 959, 958, 920 OK ABOVE CEILING 241 EXCEPT AS NOTED. |
|
| 08/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | OK LIGHTING IN ADITORIUM 241 OK ELEVATOR LOBBY & HALL 301 OK CANS SOFFIT 372 OK PDU - A1a & b, PDU - B2a & b SUPPORT VDV CABLEING AUDITORIUM (241) PER 300.11 SEAL UNUSED CONDUIT OPENING UNDER SERVER ROOM FLOOR |
|
| 08/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | OK MECHANICAL ROOMS FOR CONTROL WORK (ACC) BOTH EAST & WEST 5TH FLOOR THRU 9TH FLOOR DID GENERAL WALK THRU FOR COMM ROOMS |
|
| 08/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HARD LID SOUTH OF ELEVATOR LOBBY 7TH FLOOR 2) OPEN UP FLOOR ON 5TH FLOOR TO INSPECT PLUG, PLAY WIRING AND EQUIPMENT 3) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING IN A/C CONTROL CABINETS 250.8 4) ON 5TH FLOOR WE HAVE OPEN JUNCTION BOXES ABOVE CEILING 5) OK WALLS ROOMS 246-250 2) OK P7EA,P7EB,UPS7E,SB7E,H7E,P7WA,P7WB,UPS7W,SB7W 3) MEET WITH DAN FOR PLUG AND PLAY-INSTRUCTED WHAT TO OPEN FOR TOMORROW ON 5TH FLOOR |
|
| 08/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SB3E,TS83E,UPSB3DB,TOPSBRDB,UPSB1DB,TUPSBLDB,UPSA1DB,TUPSA1DB,UPSA2DB,TUPSA2DB,UPSA,UPSB 2) SECURE XFMR P3EA,UPSA BY PASS,UPSA,UPSB BY PASS 3) VERIFY LISTING FOR ORANGE EMT AND PLENIUM RATING |
|
| 08/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANN HALLS 925 & 935, OK CANS SOFFITS 925 AND OK WALLS 369-372 HALL 366 2) NOTE: NO MORE THAN 360 DEGREE IN RUNS, JUNCTION BOX ACCESS AND CONDUIT SUPPORTS WITHIN 3' 3) FIXTURES WITH DBL END TUBES AND BALLAST 410.73 (G) 4) SWITCH BOARD DSCPA 408.3 |
|
| 08/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK UPS-A-ODD, UPS A & B WITH BATTERY COMPARTMENTS, P3EA, HL3E, UPS3E, H3E, TUPS3E, BUSS PLUGS H3E, HL3E 2) OK WALLS WEST OF COLUMN 'D' 7TH FLOOR 3) FINISH BOTLING XFMR TP3E 4) FINISH XFMR'S GROUNDING 5) SUPPORT SWITCH 90 DEGREES ON 7 |
|
| 08/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 256-267 AND 280 2) OK PANEL PSBCP, TSBCP2, HDC, ATS-A, ? & C AND STS 3) UPS-B-ODB |
|
| 08/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS WEST OF COLUMN "D" 8TH FLOOR |
|
| 08/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 08/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH WALLS 8TH FLOOR WEST OF "D"-STRAPPINJG AND KO'S SEALS 2) SUPPORT VDV CABLING ABOVE HARD LID HALL NORTH OF CORE AND ELEVATOR LOBBY 725.8 |
|
| 08/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ELEVATOR LOBBY LID 9TH FLOOR 2) OK ROOM WALLS 360 AND 377 3) BROKEN SECURITY FLEX 9TH FLOOR LOBBY 4) FINISH SWITCHES 2ND FLOOR WALLS |
|
| 08/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | WALLS ON 3 OK | |
| 08/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ELEVATOR LOBBIES 3-9 EXCEPT LIGHTING CONTROLS 2) OK CLOUD ELEVATOR LOBBY 8TH FLOOR 3) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 4) BROKEN JUNCTION BOX |
|
| 08/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ON 9 & 10 LOOSE FITTINGS AND STRAPS 2) BOND JUNCTION BOX 3) FINISH ELEVATOR LOBBIES 4) FINISH WALLS ON 9TH FLOOR |
|
| 07/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 9 TI WALLS OK | |
| 07/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONNECTIONS FOR 2 LIEBERT UNITS 2) OK CONDUIT & BOXES 2ND FLOOR EAST OF 'D' SOUTH OF CORE AND ROOMS 254 & 255 3) FINISH PLUG AND PLAY WIRING & BOXES 2ND FLOOR |
|
| 07/26/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELEVATOR LOBBIES: 1) TIGHTEN LOOSE FITTINGS 2) PROPERLY SUPPORT CONDUITS 3) BROKEN FLEX 8TH FLOOR (FIRE ALARM) |
|
| 07/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINSIH ROOM 534 2) NEED BANG PLATES 4TH FLOOR 8TH FLOOR: 1) OK FLOOR WEST OF COLUMN D 2) OK TV 1-4, 25-28 |
|
| 07/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GENERAL WALK THRU |
|
| 07/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 6 CANS WEST END 241 2) OK CANS HALL IN 240 COLUMN B.5 TO E 3) OK WALLS ROOM 923 4) OK WALL 240 AGAINST CORE |
|
| 07/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL WEST OF COLUMN 'D' 4TH AND 5TH FLOORS 2) FILL UNUSED OPENING JUNCTION BOX ON 5TH FLOOR 3) FINISH BANG PLATES ON 4TH FLOOR |
|
| 07/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH WALL WEST OF 'D' ON 5TH FLOOR 2) PROTECT M/C CABLE BASE PLATES 4TH FLOOR WALLS WEST OF 'D' |
|
| 07/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROTECT M/C CABLE AT BASE PLATES | |
| 07/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL EAST COLUMN "D" EXCEPT ROOMS 934,935,936,937,938,939 AND 940 |
|
| 07/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SECURE RACEWAYS TO FLOOR UPS ROOM 2) OK TO USE FLEX CONDUIT TO TRANSITION DUE TO SPACE |
|
| 07/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH WALL 9TH FLOOR |
|
| 07/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH WALLS 9TH FLOOR 2) PROTECT M/C CABLE AND FLEX CABLE FROM CORROSION 300.7 |
|
| 07/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANS HALL CEILING ON 4TH FLOOR WEST |
|
| 07/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FLOOR WEST OF COLUMN 'D' FOR CONDUIT, BOXES AND TV'S 1-4, 25-28 AND RF'S 1 & 2 |
|
| 07/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 4 ON FLOOR WEST OF COLUMN 'D' 2) OK TV'S 1-4, 23-26 AND RF'S 1 & 2 3) OK PLUG AND PLAY ON 4TH FLOOR WEST 'D' 4) OK HARD LID 481 5) FINISH WALLS-PARTIAL ROCK WITHOUT INSPECTIONS |
|
| 06/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS EAST COLUMN 'D' 4TH FLOOR |
|
| 06/29/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SOFFIT 340,344,346,349 FOR 4TH FLOOR PATIO |
|
| 06/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1 OK HARD LIDS 501,601,701 & 801 EXCEPT AS NOTED 2) OK EAST WALL 852 AND 821 3) MISSING EM LIGHTS AT 501 |
|
| 06/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/23/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/22/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) GENERAL WALK THRU AND ANSWER QUESTIONS |
|
| 06/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RF3-3,4 2) OK LID 446 OK TV 3-1,2,3,4,5,,7,9,12,13,14,15,16,19,25 AND 26 3) OK WALLS 259,262,254 AND 255 REDO 4) AFTER CORRECTIONS OK FLOOR BOXES,CONDUITS NORTH 1/2 AND EAST END OF 3RD FLOOR 5) PROTECT FLEX AND M/C CABLES 259 AND 262 ON CORE WALL 6) FINISH ROOM 241-AUDITORIUM |
|
| 06/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 746,764 AND WEST HALL IN FRONT OF BATHROOM LIDS 2) OK 846, 864 HARD LIDS, OK 8TH FLOOR WALLS EAST OF COLUMN D |
|
| 06/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 9TH FLOOR BOXES AND CONDUIT, PLUG AND PLAY & TV'S MAKE UP 8-22,24-27 AND 32-34 2) SECURE M/C IN WALLS 3) MISSING M/C TO DATA BOX RECEPT |
|
| 06/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 4TH FLOOR CONDUIT AND BOXES, PLUG AND PLAY AND TV'S MAKE UP 5-22, 27, 28, EAST OF COLUMN D 2) OK HARD LID 546, 646 AND 764 3) NEED JUNCTION BOX ACCESS 4) STRAP FLEX TO 4.27 |
|
| 06/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | DISC AT BUS-DUCT TO HE PANEL LEVELS 5-9 OK HE TO VDF AND AIR HANDLERS OK LEVELS 5-9 |
|
| 06/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HALL 615 CANS AND CONDUIT 2) NOTE: JUNCTION BOX ACCESSIBILITY |
|
| 06/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SEPERATION FOR EM LIGHTING AND NORMAL LIGHTING AT HALL |
|
| 06/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 9TH FLOOR CONDUIT PLUG + PLAY EAST "D" 1. SUPPORT VDV CABLEING 725.8, 760.24, 770.24, 800.24 2. MEET WITH HECTOR ACC. DISCUSSED WORK BY HIS COMPANY A. CONTROL PANELS CANNOT USE SHEET METAL THREAD SCREWS 250.8 B. SUPPORT CONDUIT ENTERING EAST SHAFT IN ROOF C. TIGHTENING HOUSE FITTINGS |
|
| 06/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC IN WALLS EAST OF COLUMN D 2) FINISH T STAT CONDUITS IN WALLS 7TH FLOOR |
|
| 06/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 6TH FLOOR: 1) SEPERATE EM LIGHTING FROM NORMAL LIGHTING IN RACEWAYS 2) NEED JUNCTION BOX ACCESS ABOVE HARD LIDS 5TH FLOOR: 1) NEED JUNCTION BOX ACCESS ABOVE HAD LIDS 2) OK CANS HALL 554 3) VDV CABLING UNDER FLOOR 725.8, 760.24, 770.24 & 800.24 |
|
| 06/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TV-6,7,8,9,11,12,13,14,15,16,17,21,23,24,29 AND 30 8TH FLOOR 2) 9TH FLOOR: NO MORE THAN 360 DEGREE IN CONDUIT RUNS (CEILING) 2) FLEX FOR PLUG AND PLAY BROKEN IN WEST ELECTRIC ROOM ROOF: 1) TIGHTEN LOOSE FITTINGS 2) 629 COVERED WITHOUT INSPECTION |
|
| 05/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) SES-A BRKR HGA NEED TO SEE TORQUED IN. 2) PNL HGA OK TO ENERGIZE WITH PROPER LOCK-OUT PROCEDURES. PNL MPOP OK TO ENERGIZE TO DOMESTIC WATER PUMP CONTROLLER. |
|
| 05/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY PLENIUM RATING FOR WHITE EMT 2) TIGHTEN LOOSE FITTING AH 1,2,3 |
|
| 05/20/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS 6TH FLOOR-WALLS MISSING AND DATA AS PREVIOUS INSPECTIONS |
|
| 05/18/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DATA RUNS PER PLANS AND 725.8 NEED TO BE SUPPORTED 2) DATA CONDUITS LOOSE FITTINGS, SUPPORT WITHIN 3' OF FLOOR STUDS 3) FINISH WALLS 629, 636 AND 637 |
|
| 05/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS EXTERIOR 353, 354 AND 349 2) FINISH 6TH FLOOR |
|
| 05/16/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MISSING PLUG AND PLAY UNDER FLOOR AT 5TH FLOOR 2) OK UNDER FLOOR 612 |
|
| 05/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 05/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT M/C CABLE AT FLOOR SMALL BATHROOM #8 2) PROTECT CONDUITS FOR VDV CABLING FROM SHARP METAL EDGES #5 |
|
| 05/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT DATA AND SIGNAL SENDING CABLES, VDV 725.8, 770.24, 800.24 AND AS MARKED ON AV PLANS 2) SUPPORT CONDUITS WITHIN 3' OF FLOOR FOR STUBS DOWN |
|
| 05/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 5TH FLOOR: 1) FINISH SUPPORTING CONDUITS GOING DOWN |
|
| 05/06/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH STUBS DOWN TO WITHIN 8" OF FLOOR TO CHECK FITTINGS AND SUPPORT |
|
| 05/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EAST SIDE 211 | |
| 05/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ON CORE 206, 207, 208, 211 & 202 OK WALLS SOUTH SIDE EXTERIOR OK WALLS 254, 255, 241, 362-366 OK SOUTH WALL 364, 370 |
|
| 04/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/27/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BOXES AND CONDUITS 4TH LEVEL WITH WIFI AT ENTRANCE |
|
| 04/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WAITING ON ANSWERS FOR COLD CATHODE LIGHTING |
|
| 04/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/11/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/05/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CORE WALLS 2) NO PROGRESS ON 4 TERRANCE |
|
| 03/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/31/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 2) OK AUDITORIUM 241 WALLS 3) OK 3RD FLOOR NORTH WALL AS MARKED |
|
| 03/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RUNS FOR TI AT BATHROOM WALLS-CONDUIT UP WALLS |
|
| 03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK EXTERIOR WALLS 2) FINISH 511,502,513,STAIRWELL AND PHYSICAL PROTECTION OF M/C |
|
| 03/21/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROTECT M/C IN STUDS |
|
| 03/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3RD FLOOR AUDITORIUM AS MARKED |
|
| 03/15/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/09/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TODD STATE NOT READY FOR INSPECTIONS |