Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/24/2012 BUILDING - FINAL Approved
11/21/2011 BUILDING - FINAL Partial Approval
11/16/2011 BUILDING - FINAL Partial Approval
11/10/2011 BUILDING - FINAL Partial Approval WALKED 1-4
11/01/2011 BUILDING - FINAL Partial Approval LEVELS 5-R00F FINAL
10/27/2011 BUILDING - FINAL Partial Approval LEVEL 8 CORRECTIONS FOLLOW:

1) firestop all 4" pipe chases and penetrations in comm rooms
2) light fixture missing west wall (8087)
3) outlet covers missing west hall
4) water heater in west mechanical now powered (connect wiring)
5) firestop breakroom sink penetration into shaft membrane (west)
6) complete plumbing to ice machine wastes
7) secure plug & play outlets
8) finish cable rails stair 6
9) outlet covers missing 8076
10) comm runs incomplete 837,849,842,831, etc
11) need access to mech 8E and elec rooms; all equipment to be properly labeled and electrical panel schedules to be made up.
10/27/2011 BUILDING - FINAL Partial Approval LEVEL 7 CORRECTIONS FOLLOW:

1) Occupancy sensors and comm runs incomplete in several areas.
2) firestop unused chases in comm rooms
3) secure plug & plays
4) label all mechanical equipment
5) cover outlet over door M7E
6) need access to elec rooms...all panel schedules to be in place
7) install drains for ice machines
8) door at lactation room may not exceed 5#'s force to open
9) outlet covers needed 7076, 752, etc (comm boxes)
10) finish cable rails at stair 6
11) flash rings needed a microwave plug receps (west break room lower cabinet
12) wire water heaters mech 7W...also tprv must terminate above flood rim of drain pan
13) fixture missing payroll 7085
10/25/2011 BUILDING - FINAL Partial Approval For roof and all floors:

1) Elevator Certificate
2) Air balance reports
3) Mechanical system commissioning
4) Special inspection certificate for structural
5) Potable water steriliation report
6) Lightning supression report

R1) Seal conduits and chases penetrating roof
R2) Label all mechanical equipement
R3) support condensate line north side of elevator penthouse
R4) complete all work in electric room, including labeling and panel schedules
R5) Support conduit & finish wiring for mini-split condensor
R6) Provide permanent cap for grease duct
R7) Secure conduit south side of penthouse
R8) check sprinkler pipe support at top of stair 1
10/25/2011 BUILDING - FINAL Partial Approval For 9th floor:

Elevator Certificate
Air balance reports
Mechanical system commissioning
Special inspection certificate for structural
Potable water steriliation report
Lightning supression report

and

1) firestop conduit openings in comm rooms
2) mens HC water closet to be 16'--18" from side wall (not 18.5")
3) finish electric runs to roof
4) permanent panel schedules and labels needed in electric rooms
5) complete electrical fixturing in board room
6) complete AV rooms, and clarify if you want separation from mech room to main AV room
7) provide permanent labels on all mechanical equipment
8) connect water heater in west mechanical
9) plug & play systems to be properly secured to floor
10) provide flash rings at all microwave plug receptacles in cabinets
11) hang all doors
12) complete zone 2 wiring in room 955
13) check for leak that damaged ceiling tiles in room 954
14) finish comm links to deck
15) finish cable rails at stair 6
16) fire stop at alarm strobe outlet just inside stair 1.
10/24/2011 BUILDING - FINAL Partial Approval