Permit: T10CM03442

Parcel: 135030160

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/08/2011 FRAMING Approved IVRS - Inspection :*
03/03/2011 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ELECTRIC COMPLETE
2) ADD BANG PLATES THROUGHOUT
3) 1 1/4" FOR ROMEX, 1 1/2" FOR PLUMBING
4) NEED TO BOND GAS PIPING
5) J-BOX NEEDS TO BE ACCESSIBLE
6) BLOCK DUCT CANS
7) LAUNDRY P-TRAP NEEDS TO BE MINIMUM 18" FROM RECEPTOR BOX
8) NEED TO HARD PIPE DRYER VENT-NO FLEX PIPE ALLOWED IN WALLS COVERED WITH SHEETROCK
9) COMPLETE ALL FRAMING DETAILS TO PLANS
10) COMPLETE DUCT WORK AT TRANSITION
02/22/2011 FRAMING Not ready for Inspection IVRS - Inspection :*
02/17/2011 FRAMING Not ready for Inspection IVRS - Inspection :*