Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM03415
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2011 | PLUMBING - INTERMEDIATE | Approved | ||
01/11/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) STRAP 2" HORIZONTAL DRAIN TO SINK/LAV 2) SUPPORT WATER CLOSET STUB OUT 3) PLUMBER NOTE THAT A N/H BAND IS NOT THE CORRECT COUPLING FOR N/H X 51-SHOULD HAVE USED A MISSION BAND 4) NO CORRECTION NECESSARY AT THIS TIME |
|
01/10/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MATERIAL SCHEDULE ON SITE 2) SINK REQUIRES CLEANOUT 3) EXISTING SINK NOT PLUMBED TO CODE 4) MAY NOT INTERMINGLE MATERIAL TYPES 5) ADD HANGERS AS REQUIRED |
|
01/05/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE A PLUMBING FIXTURE AND MATERIAL SCHEDULE 2) OK TO COVER RELOCATED SINK (P-3) AFTER VERIFICATION OF MATERIAL TYPE 3) SINK (P-3) AT DRAW STATION REQUIRE CLEANOUT 4) EXISTING SINK CONNECTED TO 3" WASTE HAS BEEN RE-PIPED INCORRECTLY. THE TRAP WEIR MAY NOT BE ABOVE THE POINT OF VENT. REQUIRES DRAINAGE FITTINGS |