Permit: T10CM03415

Parcel: 10821328B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM03415

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2011 PLUMBING - INTERMEDIATE Approved
01/11/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) STRAP 2" HORIZONTAL DRAIN TO SINK/LAV
2) SUPPORT WATER CLOSET STUB OUT
3) PLUMBER NOTE THAT A N/H BAND IS NOT THE CORRECT COUPLING FOR N/H X 51-SHOULD HAVE USED A MISSION BAND
4) NO CORRECTION NECESSARY AT THIS TIME
01/10/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) MATERIAL SCHEDULE ON SITE
2) SINK REQUIRES CLEANOUT
3) EXISTING SINK NOT PLUMBED TO CODE
4) MAY NOT INTERMINGLE MATERIAL TYPES
5) ADD HANGERS AS REQUIRED
01/05/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A PLUMBING FIXTURE AND MATERIAL SCHEDULE
2) OK TO COVER RELOCATED SINK (P-3) AFTER VERIFICATION OF MATERIAL TYPE
3) SINK (P-3) AT DRAW STATION REQUIRE CLEANOUT
4) EXISTING SINK CONNECTED TO 3" WASTE HAS BEEN RE-PIPED INCORRECTLY. THE TRAP WEIR MAY NOT BE ABOVE THE POINT OF VENT. REQUIRES DRAINAGE FITTINGS