Permit: T10CM03415

Parcel: 10821328B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/06/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/05/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PANEL FEEDER J-BOXES NOT ACCESSIBLE
2) SUPPORT MC WITHIN 12" OF J-BOX OR DEVICE PER CODE