Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM03411
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VDV CABLING TO BE PER 725.3 & 8, 760.3 & 24, 800.3 & 24 AND 300.11 2) FINISH PREVIOUS ITEMS 1, 3, 4 & 5 3) OK PVC SENSOR LOOP |
|
05/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) REMOVE OLD WIRING BACK TO LAST JUNCTION BOX, SUPPORT ANY BOXES NOT INSTALLED , NOT CODE COMPLIANT AT TIME OF INSTALL AND CAP OR CLOSE UNUSED OPENINGS 2) PHYSICALLY PROTECT M/C CABLE IN SHALLOW DRILLED HOLES 300.4 3) PLEASE PROVIDE INFORMATION ON COMPOUND IN FLOOR AROUND EMT CONDUIT 4) HAV ENGINEER PROVIDE LETTER AUTHORIZING USE OF 1/2" EMT IN SLAB AND M/C CABLE USAGE 5) NEED TO INSPECT ALL VDV CABLING RUNS 725.3 & 8AND 800.3 &24 |
|
05/13/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) NO ANSWER AT DOOR-NO MSG 2) RECALL INSPECTION AND LEAVE MSG |