Permit: T10CM03400

Parcel: 12517039A


Addresses:

3841 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM03400

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/22/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DWV NOT INSTALLED PER PLAN
2) DWV NOT INSTALLED PER CODE, SEE SECTIONS 311.4 ALSO 1003.3, 707.6 AND 901
3) INSTALL PIPE SUPPORTS AS REQUIRED BY UPC 310.4, 313.1 AND 314.4
4) ACCESS TO ROOF NEEDED TO INSPECT VTR LOCATION
5) WH DRAIN PAN HAS NOT BE INSTALLED
6) ALL COPPER TUBING SHALL BE INSTALLED PER 310.3 AND INSTALLATION STANDARD #3 SECTION 2.3