Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FOUND VERIFICATION OF LISTING FOR SENSOR SYSTEM 2) MAY HAVE ACCESSIBILITY CONCERNS 3) OK WALLS WITH SYSTEM |
|
| 03/30/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CE IS A SELF CERTIFICATION NOT A NRTL |
|
| 03/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY LISTING TRUDO ANTENNAS AND ACCESABILITY AN SYSTEM ASSEMBLIES |
|
| 03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOX OVER FILLED 2) PROTECT M/C AT SHOW WINDOW AS DISCUSSED 3) FINISH SENSOR 4) OK WALL, HARD LIDS AND FLOOR AS DISCUSSED, EXCEPT SENSOR 5) RECEIVED LETTER FOR M/C CABLE |
|
| 03/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SERCURE M/C AND CONDUIT ON HORIZONTAL RUNS & WITHIN 12" FOR M/C 2) NEED LETTER FROM ENGINEER AUTHORIZING USE OF M/C CABLE 3) OK FRONT AND REAR SALES AREA WALLS 4) EXTERIOR SUBJECT TO LETTER |